NEC Quick-Reference Guide

A working-reference summary of commonly used National Electrical Code tables and rules of thumb. Based on the 2023 NEC. Always verify against the current adopted code cycle and local amendments before applying to a real design.

Conductor Ampacity (Copper, 3 or fewer in raceway)

NEC Table 310.16

AWG / kcmil60°C (140°F)75°C (167°F)90°C (194°F)
1415 A20 A25 A
1220 A25 A30 A
1030 A35 A40 A
840 A50 A55 A
655 A65 A75 A
470 A85 A95 A
295 A115 A130 A
1/0125 A150 A170 A
2/0145 A175 A195 A
4/0195 A230 A260 A
250 kcmil215 A255 A290 A
500 kcmil320 A380 A430 A

Values assume 30°C ambient, THHN/THWN-2 or equivalent 90°C-rated insulation. Apply ambient-temperature and conductor-count derating (Table 310.15(B) & (C)) for anything outside this base case, and terminate at the temperature rating of the equipment (usually 60°C ≤100 A, 75°C >100 A per 110.14(C)).

Conduit Fill

NEC Chapter 9, Table 1

# of conductorsMax fill
153%
231%
3 or more40%

Fill is based on conductor OD (with insulation), not copper area. Use Annex C tables for a direct "conductors per trade size" lookup once conductor type and conduit type are known.

Box Fill

NEC 314.16(B)

ItemVolume allowance
Each conductor1× conductor size
All grounds (combined)1× largest ground
Each device (2 max csv)2× largest conductor
Internal clamp1× largest conductor

"Volume allowance" is per conductor size, then summed against the box's rated cubic-inch capacity (Table 314.16(A)).

Grounding Electrode & Equipment Grounding Conductors

NEC Table 250.66 (GEC) & Table 250.122 (EGC)

Service / OCPD ratingCopper GECCopper EGC
≤100 A#8 AWG#8 AWG
≤200 A#4 AWG#6 AWG
≤400 A#2 AWG#3 AWG
≤600 A#1/0 AWG#1 AWG
≤1000 A#2/0 AWG#2/0 AWG

GEC sizing is driven by the largest ungrounded service-entrance conductor (250.66). EGC sizing is driven by the rating of the overcurrent device ahead of the equipment (250.122), and is a separate calculation — don't conflate the two.

Voltage Drop

VD = (2 × K × I × D) ÷ CM Single-phase. K ≈ 12.9 (copper) or 21.2 (aluminum) · I = load current (A) · D = one-way distance (ft) · CM = conductor circular-mil area. For three-phase, multiply by 0.866 instead of 2.

NEC doesn't mandate a voltage-drop limit outright, but the informational note under 210.19(A) and 215.2(A) recommends ≤3% on branch circuits or feeders, and ≤5% combined feeder + branch circuit.

Rules of Thumb Worth Remembering