Transformer Sizing & Protection
Pick a transformer size, get the maximum primary and secondary overcurrent protection, and size the conductors, bonding jumper, and grounding electrode conductor. Every result shows the NEC section it comes from.
NEC 2023 / 450.3 / 240.4 / 240.6 / 240.21(C) / 250.30 / 250.66 / 250.102 / 250.122 / Table 310.16
Transformer
System
Protection
Size the transformer from a load
Spare capacity is a design choice, not an NEC requirement. Use the load calculated per Article 220.
One-line
Updates as you change the inputs. Fault current assumes an infinite source, which gives the worst case.
Full-load current
Fault current
Secondary terminals, infinite source: Isc = FLA × 100 / %Z
110.9, 110.10
Bonding & grounding
250.30(A), Table 250.102(C)(1), Table 250.66, Table 250.122
Overcurrent protection
| Device | NEC limit | Maximum | Selected |
|---|
Conductors
Table 310.16, 110.14(C)(1), 240.4(B), 240.4(D), 240.21(C), 310.10(G)
No ambient or fill adjustments are applied. Apply 310.15(B) and (C) for your installation.
Design checks
Reference tool for design checks. Based on NEC 2023 (NFPA 70). Verify every result against the code edition adopted by your jurisdiction, the transformer nameplate, manufacturer data, and your authority having jurisdiction before using it in construction documents.